HIGH FREQUENCY ONLINE 1-3K/S SERIES | |||||||
TECHNICAL PARAMETERS | |||||||
Model | SDH1K | SDH1KS | SDH2K | SDH2KS | SDH3K | SDH3KS | |
Rated Capaticy | 1KVA/0.7KW | 2KVA/1.4KW | 3KVA/2.1KW | ||||
Input | Rated volttage | 220VAC | |||||
Voltage Range | 115-300VAC | ||||||
Frequency Range | 50/60Hz(Adjustable by Software) | ||||||
Power Factor | >0.98 | ||||||
Output | Voltage | 220×(1±2%)VAC | |||||
Frequency | 50Hz±0.1%(Battery Mode) | ||||||
Wave Form | Pure Sine Wave | ||||||
THD | Linear Load≤3%,Non-linear Load≤6% | ||||||
Overload Capatity | Mains Model:While Load>105-150%,30Sechonds;Whild Load>150%,300MS;Switch into Bypass Mode and Alarm Battery Model:While Load>105-150%,30Sechonds;Whild Load>150%,300MS;Shut down the Output and Alarm | ||||||
Current Crest Factor | 3:01 | ||||||
Battery | Type | VRLS Batteries | |||||
Nominal Voltage | 36VDC | 72VDC | 96VDC | ||||
Backup Time(Full/HalfLoad) | 5/15Min | Flexible | 5/15Min | Flexible | 5/15Min | Flexible | |
Transfer Time | Zero(The Main and Battery) | ||||||
Protection Ability | Overload,Short Circuit,Over Voltage,Under Voltage Over heat,TVSS | ||||||
Display | LED | UPS Working Status Indicator,Battery Capacity,Load | |||||
LCD | UPS working Status Indicator,Input&Output Voltage,Frequency,Battery Voltage&capacity,Load,Temperature | ||||||
Alarm | Battery Status,Abnormal Mains,Under Battery Voltage,Overload,Failure Sound and Lamplight Alarm | ||||||
Niose(1Meter Distance) | <45dB | <50dB | |||||
Communication Interface | RS232 | Standard RS-232 | |||||
Intelligent Slot | Compatible with optional SNMP Card,AS400 Card | ||||||
Operation Environment | Temperature | 0~40℃ | |||||
Humidity | 0-95%(Non-Condensating) | ||||||
Net Weight(Kg) | 14 | 7.5 | 32 | 15 | 33 | 16 | |
UPS Dimension(W*D*H)MM | 145×400×220 | 192×460×340 |
•Personal computer
•Work station
•Ideal power supply protection for POS systems
1.Its cut-edge digital technology of DSP (Digital Signal Processor), can greatly improve the products performance and system reliability, and deliver a compact integration with higher power density;
2.Output power factor up to 0.8 - applicable to the tendency of future load evolution, and deliver higher payload capacity;
3.Total power factor up to 90% can minimize the power loss of UPS and save utilization cost for user;
4.Emergency Power Off (EPO): UPS can be instantly shut off in case of any emergency;
5.Compliance with EMC requirements of IEC61000-4, provide your device a clean electric environment.6.Active power factor correction (PFC) technology allows the input power fact or approaching to 1 , dramatically reducing the immunity on utility grid;
7.Excellent input frequency range makes UPS suitable to different power supply devices, i.e. generator set;
8.Parallel Kit: realize the parallel extension and redundancy function, offer more flexibility and safety for user's power supply planning;
9.Compact Design, Lower Noise.