Model | C1K(S) | C2K(S) | C3K(S) |
Capacity | 1KVA/800W | 2KVA/1600W | 3KVA/2400W |
Input |
|
||
Phase | Single phase,1 wire +N+G | ||
Nominal Voltage | 220VAC | ||
Voltage Range | 120-276VAC | ||
Frequency Range | 50Hz or 60Hz±10% | ||
Power Factor | >0.99(100% Load) | ||
Output |
|
||
Output Voltage | 110V/120V/220V/230V/240VAC | ||
Voltage Regulation | ±1% | ||
Frequency Range | Synchronized 46-54Hz(Line mode)50/60Hz±0.2Hz(battery mode) | ||
OverLoad | 105%-125% for 50 seconds then transfer to by pass;125%150%:for 0.3 second then transfer to bypass. | ||
Crest Power | 3:01 | ||
Wave Form | Pure sine wave | ||
Harmonic Distortion | ≤3%THD(Linear Load) | ||
Transfer time | 0ms(Line to battery mode;4ms(Inverter to bypass mode) | ||
Protections | Overload/short circuit/over temperature/Surge/line abnormal | ||
Efficiency | ≥95% | ||
N.W. (Kg) | 11/6.5 | 26/12. | 26.5/12.5 |
SIZE (WXDXH(mm): | 145x400x220 | 192x460x340 | 192x460x340 |
Pure Sine Wave Output
Zero Transfer Time
Zero Live Wire Input False Detection Function
Humanization Bypass Output
Input Power Factor Correction
DC Start-up
Bypass Protection
Automatic Start-up Function
Long Endurance Power Supply Design
Powerful Charge Up Ability
Self-Check and Auto Restart Function
Equipped with Intelligent Slot